蘇州家一體化振動變送器廠家;
一體化振動變送器 主要由振動速度傳感器、功能轉換電路、數(shù)字顯示三部分組成。可廣泛用于:風機、壓縮機、泵等大型旋轉機器。測量軸承座、機殼等振動。輸出電流(或電壓)信號,便于同計算機系統(tǒng)(DCS等)聯(lián)接。它直接安裝在機器外部,故安裝、使用、維護極為方便。它直接顯示振動值(烈度或位移)極大方便了維護人員實時了解機器運行情況。
▲安裝方式:在機器軸瓦蓋上開一個M10x1.5孔(有效 深度10mm),直接用Mm10x1.5螺栓固定。航友產品自帶;▲輸出精度: 3% ▲負載能力:不大于500Ω▲測量參數(shù):振動位移、振動速度(烈度)值。▲兩種方式:1、直接顯示振動值 2、不直接顯示振動值選型 A B C D E位移型 :HY9200A–D–A–B–C-D-E
A: 量程 00:100μm 01:200μm 02:300μm 99:客戶要求 B:電源 00:-24V 01:+24V 99:客戶要求C: 輸出 00:4-20mA 01:1-5V 99:客戶要求D:接線方式 00:直接出線防水型 01;航空插頭
E: 鎧裝選配
00:無鎧裝
01:有鎧裝
A B C D E烈度型 HY9200A–A–B–C–D-EA: 量程: 00:0-10mm/s 01:0-20mm/s 02:0-30mm/s 99:客戶要求 B:電源 00:-24V 01:+24V 99:客戶要求C: 輸出 00:4-20mA 01:1-5V 99:客戶要求D:接線方式 00:直接出線防水型 01:航空插頭
E: 鎧裝選配
00:無鎧裝
01:有鎧裝
選型常用型號:HY9200A-V-A01-B01-C01-D00-E00
代表:航友牌一體化振動變送器
航友HY9200A 振動速度型量程:0-20mm/s;供電24V DC;對應輸出4-20mA;直接出線防水型,無鎧裝;常用于風機,水泵,電機,軸瓦振動在線監(jiān)測;直接連接DCS系統(tǒng)。
EJA430A壓力變送器用于測量氣體、液體和蒸汽的壓力,然后將其轉變成4-20mADC的電流信號輸出。EJA430A也可以通過BRAIN手操器或CENTUM CS/μXL或HART 275手操器相互通訊,通過它們進行設定和監(jiān)控等。
JH3351DP/GP智能遠傳差壓/壓力變送器 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
![]() | 遠傳裝置是用于防止管道中的介質直接進入變送器里的壓力傳感器組件,它與變送器之間是靠注滿流體的毛細管連接起來的。用于測量液體、氣體或蒸汽的液位、流量和壓力,然后將其轉變成4~20mA DC信號輸出。 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
JH3351DP/GP差壓/壓力變送器帶上遠傳密封裝置后,就成為JH3351DP/GP遠傳差壓/壓力變送器,它仍具有JH3351DP/GP差壓/壓力變送器的各種特點。可與HART手操器相互通訊,通過它進行設定,監(jiān)控。可避免被測介質直接和變送器的隔離膜片接觸,這種測量方法適用于下述幾種情況: 1、被測介質對變送器接頭和敏感元件有腐蝕作用; 2、需要將高溫被測介質與變送器隔離; 3、被測介質由引壓管引出易固化或結晶; 4、被測介質中有固體懸浮物或高粘度易堵塞變送器接頭和壓力容室; 5、更換被測介質需要沖洗而不容交混; 6、必須保持衛(wèi)生,嚴禁污染。 可提供多種結構材料,遠傳裝置組件焊接結構,性強。充液腔低容積設計,減少溫度影響,根據(jù)用戶要求內充200系列硅油使用溫度-40~+149℃;耐高溫硅油,使用溫度-20~+315℃。 遠傳裝置工作壓力上限是用戶選擇遠傳裝置的額定值;工作壓力不低于3.5KPa(絕對壓力)。對腐蝕介質,選擇隔離膜片材料。 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
◆選型方式 | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
The O2X1 is a small, two-wire, loop-powered oxygen transmitter with an advanced galvanic fuel-cell sensor and linear output. It is certified as intrinsically safe and weatherproof to NEC and CENELEC codes.Besides the standard stainless steel version, the O2X1 is also available in two other packages:
The first package is a lower-cost package using Delrin for the wetted parts of the transmitter. This package has the same 1/8 in (3.175 mm) NPTF processes connections as the standard stainless steel O2X1 and is suitable for all ranges except the lowest PPM oxygen range.
The second package makes the Delrin design suitable for ambient air oxygen monitoring by providing a diffusion cut-out in the lower manifold to expose the sensor. This package comes with an aluminum mounting bracket for mounting the O2X1 to any convenient wall location.
Features and Benefits
Measures oxygen from 1.0 ppm to 25 percent
Six field-programmable ranges
Repeatability ± 1 percent of span
Self-contained cell requires no maintenance
4 to 20 mA, loop powered, 9 to 28 VDC
·產品描述 | ||
|
產品介紹 |
|
◆工作電壓:12.5-36VDC
◆輸出信號:4-20mA 二線0-40mA三線
◆測呈范圍:0-120m(最大)
◆精度:0.25、0.5
◆穩(wěn)定性:優(yōu)于0.1%/年
◆允許溫度:介質-20℃-70℃(被測介質不得結冰)
貯存-40℃-100℃
◆傳感器材料:不銹鋼1Gr18Ni9Ti
◆膜片316不銹鋼
◆密封:氟橡膠\聚四氟乙烯
◆導氣電纜材料:聚氣乙烯與丁腈橡膠復合
◆過程連接方式:外螺紋G1½.M20X1.5,法蘭
纜式靜壓液位變送器有G1 ½ M20X1.5螺紋及法蘭兩種標準的安裝方式。
◆螺紋安裝
對于直接使用G1 ½ M20X1.5螺紋安裝的變送器.供貨時提供一個G1 ½ M20X1.5圓螺 母一般安裝可有兩種方式。
1、安裝位罝已有G1 ½ M20X1.5螺紋。直接把液位變送器旋入即可.附帶的圓螺母可以不 用.也可以旋上用以放松。
2、安裝位置無G1 ½ 或 M20X1.5螺紋,可利用現(xiàn)有的∅50~∅60的光孔1或安裝帶有∅50~∅60 孔的支架.裝上液位變送器.并旋上圓螺母固定。
◆法蘭安裝
標準供貨時法蘭的安裝尺寸符合DN50 GB9119.6-88
如果安裝位置已有其他標準的法蘭安裝孔,訂貨時請注明法蘭尺寸或對應的規(guī)格及標準號.以便 滿足安裝要求。
當被測介質不穩(wěn)定時,探頭容易產生位移,從而影響測里精度.這時應將探頭固定。如果現(xiàn)場不具備固定探頭的條件.可選用配重.使探頭重量增加從而起到穩(wěn)定探頭的作用。如需選用配重, 請在訂貨時說明。
纜式靜壓液位變送器^出廠時零點及滿度都已標定。
需說明的是.滿度的標定是按用戶提供的被測介質的比重.經計算進行的干標定。由于標定條件 與使用條件很難完全一致.因此滿度指示可能會有不同程度的出入.因此在靜壓液位變送器安裝后應 對滿度進行校正。校正時使介質液位達最大值把變送器輸出值較正到20^ 000\如果現(xiàn)場條件不允許介質液面達到最大值.則可根據(jù)液位的實際數(shù)值.用下式計算出對應的電流輸出值加以校正:
其中:In 液位在n點時變送器應當輸出的電流值(單位mA)
Hn n點液位高度(單位m)
hmax 被測介質最大液位高度(即滿里程.單位m)
為提高校正精度,校正時請參考變送器出廠時的標定記錄.適當加以修正。